RKI’s paper tape monitors utilize highly sensitive colorimetric tapes to achieve interference free gas detection. The FP-330 is equipped with an easily replaceable tape that is highly specific to Formaldehyde. This model is equipped with a digital display showing the type of gas and concentration in PPM. The FP-330 will also display remaining tape life as well as an end of tape alarm.
Easily Transportable
Accurate at WHO Formaldehyde levels
Free of interference from other gases unlike Electro-chemical solutions
Easy to use and maintain
Continuous operation without interuption
Easy connection to external accessories such as remote sounder beacons , data loggers and diallers and BMS
The FP-330 has audible and visual alarms, as well as alarm relay contacts and 4-20mA output. A unique “Tape Saver mode” extends tape life in applications where high background gas levels may be present.
The FP-330 meets and exceeds OSHA and NIOSH compliance requirements, and does not respond to interfering gases (hydrocarbons, alcohols, solvents, CO, etc.) that may be present in industrial/manufacturing environments. FP 330
Model |
FP-330 HCHO 0 – 0.500 ppm |
FP-330 HCHO 0 – 1.00 ppm |
FP-330 HCHO 0 – 5.00 ppm |
Detection Principle |
Photoelectric photometry method using tape cassette | ||
Detection tape | Plug in cassette, 65-FCL-018 | ||
Detection gas | Formaldehyde (HCHO) | ||
Detection range |
0.030 to |
0.05 to |
0.3 to |
Alarm point | 1st 0.080ppm 2nd 0.300ppm |
1st 0.17ppm 2nd 0.33ppm |
1st 0.8ppm 2nd 1.7ppm |
Alarm Operation |
Latching alarm (standard) or non-latching (option) |
||
Zero Suppression |
0.030 ppm |
0.05 ppm |
0.3 ppm |
Measuring cycle |
1800 sec. |
600 seconds |
180 seconds |
Resolution |
0.005ppm |
0.01 ppm |
0.1 ppm |
Flow rate |
450ml/min. (nominal) |
||
Max. tubing length |
2m (teflon only) |
||
Accuracy |
+/-20% of indication value + 1 digit |
||
Tape operation time |
1 month with no background gas. (see note below) |
||
Alarm Indication |
Warning and alarm with audible and visual indications |
||
Self-diagnosis |
Low flow, tape cut, sensor failure, etc. |
||
External output signal |
4-20mA (load resistance: below 300Ω) |
||
Operating temperature & humidity |
5~35°C 20~60% RH (non condensing) |
||
Gas inlet/outlet |
OD 6mm with fittings |
||
Power supply & power |
100VAC to 220VAC universal power, |
||
Dimensions & weight |
Approx. 6.5″(W) x 7.8″(H) x 10.4″(D) 164 (W) x 198 (H) x 263 (D) mm, 6.5kg |
We are able to provide products and advice usually within short timescales. For product advice, servicing and enquiries, please contact our experienced team: